A
feedback controller is designed to generate an output that causes
some corrective effort to be applied to a process so as to drive a
measurable process variable towards a desired value known as the
setpoint. The controller uses an actuator to affect the process and
a sensor to measure the results.
Virtually all
feedback controllers determine their output by observing the error
between the setpoint and a measurement of the process variable.
Errors occur when an operator changes the setpoint intentionally or
when a disturbance or a load on the process changes the process
variable accidentally. The controller’s mission is to eliminate the
error automatically.
 |
| A mechanical flow controller manipulates the valve to
maintain the downstream flow rate in spite of the leakage. The
size of the valve opening at time t is V(t). The
flowrate is measured by the vertical position of the float
F(t). The gain of the controller is A/B. This
arrangement would be entirely impractical for a modern flow
control application, but a similar principle was actually used
in James Watt’s original fly-ball governor. Watt used a float
to measure the speed of his steam engine (through a mechanical
linkage) and a lever arm to adjust the steam flow to keep the
speed constant. |
An example
Consider for
example, the mechanical flow controller depicted above. A portion of
the water flowing through the tube is bled off through the nozzle on
the left, driving the spherical float upwards in proportion to the
flow rate. If the flowrate slows because of a disturbance such as
leakage, the float falls and the valve opens until the desired flow
rate is restored.
In this example,
the water flowing through the tube is the process, and its flowrate
is the process variable that is to be measured and controlled. The
lever arm serves as the controller, taking the process variable
measured by the float’s position and generating an output that moves
the valve’s piston. Adjusting the length of the piston rod sets the
desired flowrate; a longer rod corresponds to a lower setpoint and
vice versa.
Suppose that at
time t the valve opening is V(t) inches and the
resulting flowrate is sufficient to push the float to a height of
F(t) inches. This process is said to have a gain of
Gp = F(t)/V(t). The gain of a process shows how
much the process variable changes when the controller output
changes. In this case,
F(t) =
Gp V(t)
[1].
Equation [1] is
an example of a process model that quantifies the
relationships between the controller’s efforts and its effects on
the process variable.
The controller
also has a gain Gc, which determines the
controller’s output at time t according to
V(t) =
Gc (Fmax - F(t)) [2]
The constant
Fmax is the highest possible float position,
achieved when the valve’s piston is completely depressed. The
geometry of the lever arm shows that Gc = A/B,
since the valve’s piston will move A inches for every
B inches that the float moves. In other words, the quantity
(Fmax - F(t)) that enters the controller as an
input 'gains' strength by a factor of A/B before it is output
to the process as a control effort V(t).
Note that
controller equation [2] can also be expressed as
V(t) = Gc (Fset - F(t)) +
VB [3]
where
Fset is the desired float position (achieved when
the flow rate equals the setpoint) and VB =
Gc (Fmax - Fset) is a constant
known as the bias. A controller’s bias represents the control
effort required to maintain the process variable at its setpoint in
the absence of a load.
Proportional control
Equation [3]
shows how this simple mechanical controller computes its output as a
result of the error between the process variable and the setpoint.
It is a proportional controller because its output changes in
proportion to a change in the measured error. The greater the error,
the greater the control effort; and as long as the error remains,
the controller will continue to try to generate a corrective
effort.
So why would a
feedback controller have to be any more sophisticated than that? The
problem is a proportional controller tends to settle on the
wrong corrective effort. As a result, it will generally leave
a steady state error (offset) between the setpoint and the
process variable after it has finished responding to a setpoint
change or a load.
This phenomenon
puzzled early control engineers, but it can be seen in the flow
control example above. Suppose the process gain Gp
is 1 so that any valve position V(t) will cause an identical
float position F(t). Suppose also the controller gain
Gc is 1 and the controller’s bias
VB is 1. If the flow- rate’s setpoint requires
Fset to be 3 inches and the actual float position
is only 2 inches, there will be an error of (Fset -
F(t)) = 1 inch. The controller will amplify that 1 inch error to
a 2 inch valve opening according to equation [3]. However, since
that 2 inch valve opening will in turn cause the float position to
remain at 2 inches, the controller will make no further change to
its output and the error will remain at 1 inch.
 |
| The same
mechanical controller now manipulates the valve to shut off
the flow once the tank has filled to the desired level
Fset. The controller’ gain of A/B has
been set much lower, since the float position now spans a much
greater range. |
Integral control
Even bias-free
proportional controllers can cause steady-state errors (try the
previous exercise again with Gp = 1,
Gc = 2, and VB = 0). One of the
first solutions to overcome this problem was the introduction of
integral control. An integral controller generates a
corrective effort proportional not to the present error, but to the
sum of all previous errors.
The level
controller depicted above illustrates this point. It is essentially
the same float-and-lever mechanism from the flow control example
except that it is now surrounded by a tank, and the float no longer
hovers over a nozzle but rests on the surface of the water. This
arrangement should look familiar to anyone who has inspected the
workings of a common household toilet.
As in the first
example, the controller uses the valve to control the flowrate of
the water. However, its new objective is to refill the tank to a
specified level whenever a load (i.e., a flush) empties the tank.
The float position F(t) still serves as the process variable,
but it represents the level of the water in the tank, rather than
the water’s flowrate. The setpoint
Fset is the level at which the tank is
full.
The process
model is no longer a simple gain equation like [1], since the water
level is proportional to the accumulated volume of water that has
passed through the valve. That is

Equation [4]
shows that tank level F(t) depends not only on the size of
the valve opening V(t) but also on how long the valve has
been open.
The controller
itself is the same, but the addition of the integral action in the
process makes the controller more effective. Specifically, a
controller that contains its own integral action or acts on a
process with inherent integral action will generally not
permit a steady-state error.
That phenomenon
becomes apparent in this example. The water level in the tank will
continue to rise until the tank is full and the valve shuts off. On
the other hand, if both the controller and the process
happened to be pure integrators as in equation [4], the tank would
overflow because back-to-back integrators in a closed loop cause the
steady-state error to grow without bound!
|
|
The blue trace on this strip chart shows the error
between the process variable F(t) and its desired value
Fset. The derivative control action in red
is the time derivative of this difference. Derivative control
action is zero when the error is constant and spikes
dramatically when the error changes
abruptly. |
Derivative control
Proportional (P)
and integral (I) controllers still weren’t good enough for early
control engineers. Combining the two operations into a single 'PI'
controller helped, but in many cases a PI controller still takes too
long to compensate for a load or a setpoint change. Improved
performance was the impetus behind the development of the
derivative controller (D) that generates a control action
proportional to the time derivative of the error signal.
The basic idea
of derivative control is to generate one large corrective effort
immediately after a load change in order to begin eliminating the
error as quickly as possible. The strip chart in the derivative
control example shows how a derivative controller achieves this. At
time t1, the error, shown in blue, has increased abruptly because a
load on the process has dramatically changed the process variable
(such as when the toilet is flushed in the level control
example).
The derivative
of the error signal is shown in red. Note the spike at time
t1. This happens because the derivative of a
rapidly increasing step-like function is itself an even more rapidly
increasing impulse function. However, since the error signal is much
more level after time t1, the derivative of the
error returns to roughly zero thereafter.
In many cases,
adding this 'kick' to the controller’s output solves the performance
problem nicely. The derivative action doesn’t produce a particularly
precise corrective effort, but it generally gets the process moving
in the right direction much faster than a PI controller would.
Combined PID control
Fortunately, the
proportional and integral actions of a full 'PID' controller tend to
make up for the derivative action’s lack of finesse. After the
initial kick has passed, derivative action generally dies out while
the integral and proportional actions take over to eliminate the
remaining error with more precise corrective efforts. As it happens,
derivative-only controllers are very difficult to implement anyway.
On the other
hand, the addition of integral and derivative action to a
proportional-only controller has several potential drawbacks. The
most serious of these is the possibility of closed-loop
instability (see 'Controllers must balance performance with closed-loop
stability,' Control Engineering, May 2000). If the
integral action is too aggressive, the controller may over-correct
for an error and create a new one of even greater magnitude in the
opposite direction. When that happens, the controller will
eventually start driving its output back and forth between fully on
and fully off, often described as hunting. Proportional-only
controllers are much less likely to cause hunting, even with
relatively high gains.
Another problem
with the PID controller is its complexity. Although the basic
operations of its three actions are simple enough when taken
individually, predicting just exactly how well they will work
together for a particular application can be difficult. The
stability issue is a prime example. Whereas adding integral action
to a proportional-only controller can cause closed-loop
instability, adding proportional action to an integral-only
controller can prevent it.
PID in action
Revisiting the
Flow control example, suppose an electronic PID controller capable
of generating integral and derivative action as well as proportional
control has replaced the simple lever arm controller. Suppose too a
viscous slurry has replaced the water so the flow rate changes
gradually when the valve is opened or closed.
Since this
viscous process tends to respond slowly to the controller’s
efforts—when the process variable suddenly differs from the setpoint
because of a load or setpoint change—the controller’s immediate
reaction will be determined primarily by the derivative action, as
shown on the Derivative control example. This causes the controller
to initiate a burst of corrective efforts the instant the error
moves away from zero. The change in the process variable will also
initiate the proportional action that keeps the controller’s output
going until the error is eliminated.
After a while,
the integral action will begin to contribute to the controller’s
output as the error accumulates over time. In fact, the integral
action will eventually dominate the controller’s output, since the
error decreases so slowly in a sluggish process. Even after the
error has been eliminated, the controller will continue to generate
an output based on the accumulation of errors remaining in the
controller’s integrator. The process variable may then
overshoot the setpoint, causing an error in the opposite
direction, or perhaps closed-loop instability.
If the integral
action is not too aggressive, this subsequent error will be smaller
than the original, and the integral action will begin to diminish as
negative errors are added to the history of positive ones. This
whole operation may then repeat several times until both the error
and the accumulated error are eliminated. Meanwhile, the derivative
term will continue to add its share to the controller output based
on the derivative of the oscillating error signal. The proportional
action also will come and go as the error waxes and
wanes.
Now replace the
viscous slurry with water, causing the process to respond quickly to
the controller’s output changes. The integral action will not play
as dominant a role in the controller’s output, since the errors will
be short lived. On the other hand, the derivative action will tend
to be larger because the error changes rapidly when the process is
highly responsive.
Clearly the
possible effects of a PID controller are as varied as the processes
to which they are applied. A PID controller can fulfill its mission
to eliminate errors, but only if properly configured for each
application.
|